What happened at Newbury?
03 March 2011
Until the ongoing investigations are complete, it will be impossible to say exactly what caused the tragic death of two racehorses at Newbury Racecourse on Saturday.
However, electrical test equipment expert Megger can suggest a likely scenario that explains why the horses died while people in the same area were only minimally affected.The root of the problem appears to have been an underground electric cable with faulty or damaged insulation, which allowed electricity to leak into the ground. The effect of this would have been to raise the voltage of the ground around the fault.
The voltage rise would have been highest near the fault, falling away at distances further from the fault. This means that the voltage difference between a location close to the fault and one, say, twelve inches further away would have been small, but the voltage difference between a location close to the fault and one four or five feet away would have been much larger.
This is the key to the mystery, as it’s not voltage that causes electrocution, but current. And it’s voltage difference that makes current to flow.
Because people stand with their feet close together, the voltage difference between the feet of someone standing close to the fault would have been quite small, and only a small current would have flowed through their body. They would probably have felt a small electric shock, but have experienced no harmful after effects. This is exactly what the trainers reported.
The situation for horses is very different, as there is a considerable distance between their front and rear feet. This means that for a horse standing in the vicinity of the fault there would have been a big voltage difference between its front and rear feet. This would have allowed a large current to flow, with the fatal results that were seen.
Other factors would also have been involved. Horses have metal shoes that make good electrical contact with the ground, making it easy for current to flow, whereas people normally wear shoes or boots with soles that are electrical insulators and impede the flow of current.
In addition, sudden collapse from electric shock is typically the result of heart failure caused by current passing through or near the heart muscle. An electric current flowing from leg to leg in a person, however, doesn’t go anywhere near the heart, whereas a current flowing from the front to the rear legs of a horse most certainly does.
This explanation doesn’t make Saturday’s events at Newbury any less tragic, but it does offer a solution to the apparent mystery of why the horses and were affected when people in the same area were not. It also highlights the importance of regularly testing the protection systems that might have been expected to automatically disconnect the electricity supply to a faulty cable before the fault was able to cause injury and death.
Other Press Releases By This Company
- 13/08/2012 - Megger pinpoints cable faults with accuracy and ease
- 13/08/2012 - Megger acquires SebaKMT
- 13/08/2012 - Megger rewards online excellence
- 13/08/2012 - Measure phase angle quickly and easily with Megger
- 28/03/2011 - Megger catalogues contractor kit comprehensively
- 09/02/2011 - Megger’s new multimeter combines safety with versatility
- 11/01/2011 - Check voltage and more with Megger two-pole testers
- 05/01/2011 - Megger earth testers have the clamp of convenience
- 10/11/2010 - Testing to address the transformer threat
- 10/11/2010 - Megger helps keep SS Shieldhall shipshape
- 14/09/2010 - Time is running out for Megger’s money making events
- 07/09/2010 - MEGGER SUPPORT IS THERE WHEN YOU NEED IT!
- 23/07/2010 - Megger ups the ante in oil testing
- 15/07/2010 - Megger socialises online
- 06/07/2010 - Winding resistance quickly and safely with Megger
- 18/03/2010 - Megger’s EGIL simplifies breaker analysis
- 18/03/2010 - New catalogue from Megger is packed with opportunity
- 01/03/2010 - Megger provides contractors with more Business In A Box
- 13/11/2009 - Megger backs a winner with Central Trade Skills
- 04/09/2009 - Megger introduces on site training
- 28/08/2009 - Own Meggers' last ever AVO
- 31/07/2009 - Megger supports IEC 61850 for protective relay testing
- 29/06/2009 - Megger helps trainees with their tests
- 24/04/2009 - Megger measures low resistance anywhere
- 16/04/2009 - Megger has the definitive test for transformer insulation
- 27/03/2009 - Megger delivers versatility in easy relay testing
- 04/03/2009 - Megger Transformer maintenence minimises failure cover risk
- 16/12/2008 - Fancy a Business in a Box?
- 12/12/2008 - Megger Keeps the Western Locomotive Running
- 25/11/2008 - Measurement of Moisture in Oil Made Easy by Megger
- 07/11/2008 - Megger's TDR Plugs Revenue Leaks
- 14/10/2008 - The Transformer
- 13/10/2008 - Megger’s PowerDB Turns Results into Revenue
- 06/10/2008 - Megger say Goodbye to their most Popular Product
- 19/08/2008 - Condition Assessment without a Laptop
- 19/08/2008 - Transformer testing with speed and accuracy
- 17/07/2008 - Earth Testing made Easy
- 16/07/2008 - The case of the flying Megger meters!
- 14/07/2008 - Megger Helps Students Pass
- 20/05/2008 - Megger makes testing easier with Bluetooth